Detailed information reports, Figure 15 input status screen, Figure 16 dc bus / battery status – Liebert 30-130kVA User Manual

Page 32: Input status, Dc bus / battery status

Advertising
background image

Operation

24

Detailed Information Reports

Detailed information reports are available through the following numbered blocks
1. INPUT STATUS. To access this screen, start with the Mimic Display Screen. Using the arrow

keys, bracket INPUT and press SELECT. The screen displays the UPS input voltage and current

as well as additional information. Press SELECT to return to the Mimic Display Screen.

Figure 15 Input status screen

The Input Status screen displays the following real-time data:

• Input AC Volts AB, BC, CA
• Input Current A, B, C
• Input Frequency
• Inlet Air Temperature
• Outlet Air Temperature
• Heat Sink Temperature (100 and 130 kVA will display 3 temperatures, 1 for each heatsink)

2. DC BUS / BATTERY. By highlighting and selecting BATTERY from the Mimic Display Screen,

the following screen comes up, displaying DC bus voltage and the charge or discharge current.

This screen also shows BATTERY TEMPERATURE. Press SELECT to return to the Mimic

Display Screen.

Figure 16 DC bus / battery status

NOTE
On the Mimic Display Screen, items are bracketed instead of highlighted so as not to confuse

highlighting with power pathways.

NOTE
All voltage readings are phase-to-phase measurements (A-B, B-C, and C-A). All current

readings are phase measurements (A, B, and C). The metered parameter values on the

following screens are updated at one-second intervals

INPUT STATUS

A B C FREQ. 60.0 HZ

V L - L 209 209 210 TEMPS (DEG C)
I 37 37 35 INLET AIR 24

OUTLET AIR 27

HEAT SINKS

1:025 2:020 3:020

DC BUS / BATTERY STATUS

DC BUS VOLT 540

BATT VOLT 472

BATT CURR 4.1 (CHG)

BATT TEMP 25

LAST BATTERY TEST : 07/07/02

NUMBER OF BATT. ONLINE 1

C