0 introduction, 1 system description, Ntroduction – Liebert 30-130kVA User Manual

Page 11: System description

Advertising
background image

Introduction

3

1.0

I

NTRODUCTION

1.1

System Description

The role of the UPS system is to supply uninterruptible, clean power to the critical load. It maintains

a full-voltage, low-distortion output, even if the utility source power sags or becomes distorted.
If there is an outage of the source power, the UPS maintains power to the load until an alternate

source of power is activated, or until the original power source is restored. If input AC power is not

restored, the UPS maintains the load (with the battery plant) long enough that the critical equipment

can be shut down in an orderly manner. The Npower UPS module displays the rate of battery dis-

charge and calculates the amount of battery time remaining based on the actual connected load. The

time that the battery will maintain the load depends on the capacity of the battery backup plant and

the size of the load.
The system control logic automatically manages critical bus operation. System logic is resident in Dig-

ital Signal Processors (DSPs) for precise control and improved reliability.
If the critical load current exceeds the rated load of the Npower UPS system, the control logic deter-

mines the magnitude of the overload and reacts appropriately. Overloads are usually the result of

inrush current requirements. The UPS system supports loads that are 150% of the rated load for up

to 60 seconds, 125% of the rated load for up to ten minutes, and 104% of the rated load indefinitely.
If the load surpasses the overload capacity of the UPS, the load is automatically transferred to bypass

without interruption. When the load returns to within the UPS rating, it is either automatically or

manually returned (retransferred) to the UPS. How and when the load is returned to the UPS

depends on several factors: how long the overload lasted, how many overload conditions occurred

before transfer, whether there is an imminent failure of any part of the UPS, etc. In the unlikely

event of a fault within the UPS, the control logic, which continuously monitors all critical circuits

within the UPS system, transfers the load to bypass without interruption and simultaneously sets off

local and remote alarms. For a few specified faults, the UPS is shut down. The UPS can be manually

returned to service when the fault has been corrected.
The Npower UPS display system provides precise monitoring of the UPS, fast alarm response, and

quick troubleshooting. For easy manual operations, menu-driven software provides access to several

step-by-step help screens. All operator functions are performed using menu-prompted displays and a

minimum number of operator controls. Available options include external communication capability

with both automatic dial-out and dial-in features for early warning and diagnosis of abnormal condi-

tions.
The system software allows the operator or Liebert Global Services to enter application specific infor-

mation. Overload, overvoltage, battery discharge, and shutdown limits can be set by the operator. In

effect, the software is tailored for each site.
The UPS system protects critical equipment from source power disturbances and outages, load faults,

and UPS malfunctions. This triple protection virtually eliminates computer and computing equip-

ment downtime as a result of utility source power problems.