Table 3 – Liebert 30-130kVA User Manual

Page 39

Advertising
background image

Operation

31

Figure 28 External maintenance bypass switch, single-input UPS

The table below summarizes the External Maintenance Bypass switch positions and actions.

When the External Maintenance Bypass switch is in Bypass or Maintenance position, the UPSC will

assert the bypass contactor close signal and the output contactor open signal. It will also turn on the

SBS. Automatic Retransfer operations will be disabled.
If the External Maintenance Bypass switch rotates from the Bypass or Maintenance to the Normal

position, then the UPSC will keep the bypass in the ON state, thus keeping the critical bus powered

via the bypass source. The user will be able to issue a “Manual Transfer to Inverter” command pro-

vided the retransfer conditions are satisfied. The user can also issue a shutdown or a start command.
If the External Maintenance Bypass switch rotates from the Normal to the Bypass or Maintenance

position, the UPSC will assert the bypass contactor close signal and the output contactor open signal.

It will also turn on the SBS. Automatic Retransfer operations will be disabled.

Table 3

External maintenance bypass switch positions and actions

Switch position

S1-A

S1-B

S1-C

AUX

Maintenance (Service)

Open

Closed

Open

Open

Test (Bypass)

Closed

Closed

Open

Open

On Line (Transition)

Closed

Closed

Closed

Open

On Line (Normal)

Closed

Open

Closed

Closed

S1-A

S1-B

S1-C

SBS

Rect

INV

Battery

Critical load

UPS Input

IMBS