Table 9 battery voltage record, 5 torque requirements, Torque requirements – Liebert 30-130kVA User Manual

Page 107: Table 9, Battery voltage record, Table 10, Table 11

Advertising
background image

Maintenance

99

The equalizing charge time period is adjustable from zero to 72 hours and can be initiated automati-

cally or manually. Refer to Battery Equalizer on page 59.

* To be completed by Liebert Global Services customer engineer at time of start-up.

4.2.5 Torque Requirements

All electrical connections must be tight.
The next Table provides the torque values for the connections in the UPS. Use these values unless the

equipment is labeled otherwise.

Table 9

Battery voltage record

Date

Float Voltage

(Volts DC)

Nominal Voltage

(Volts DC)

Ambient Temp. (°F)

NOTE
Refer to battery manufacturer's manual for the proper torque values required for the battery.

(See battery manufacturer’s Website.)

Table 10

Circuit breakers with compression lugs (for power wiring)

Current Rating

Lb-in

N-m

400 - 1200 Amps

300

34

Table 11

Terminal block with compression lugs (for control wiring)

AWG Wire Size

or Range

Lb-in

N-m

#22 -- #14

3.5 to 5.3

0.4 to 0.6

Advertising