Figure 91 Equalize time period screen

When the battery is at full voltage (not being recharged), this selection reads EQUALIZE TIME

PERIOD (hrs). When the battery is recharging, this selection reads EQUALIZE TIME REMAINING

(hrs). After the equalize recharge time has expired, the indication returns to the preset equalize time.

Figure 92 Equalize voltage screen

The equalize voltage is also programmable. In the example above, the range is 520 to 580 volts with

the default being 540 volts.

Battery Temperature Compensation Charge

The Battery Temperature Compensation Charge screen is accessed from the Battery Management

Screen (Figure 83). The Operator can enable or disable Battery Temp Compensation function. He

can also change the compensation setting by going into the edit screen. The values are in millivolts/

degree C.

Figure 93 Battery temperature compensation charge screen

EQUALIZE TIME PERIOD

MIN MAX

0 72

000

EQUALIZE VOLTAGE

MIN MAX

520

580

540

BATTERY TEMP COMPENSATION CHARGE

15 C =

TEMPERATURE 20 C 850

20 C = TEMPERATURE 25 C 1000
25 C = TEMPERATURE 30 C 1000
30 C = TEMPERATURE 35 C 850

<

<

<

<

< <
<

<