Figure 80 list of alarm faults screen, Caution, Programmable output relay board # 1 – Liebert 30-130kVA User Manual

Page 63: Alarm / fault name, Prog relay # 1

Advertising
background image

Operation

55

If the Operator selects USER DEFINED from the RELAY ASSIGNMENTS screen, the following

screen will come up.

Figure 79 Programmable output relay board, user defined

All User Defined relays are programmable.

To begin programming the User Defined Relays, highlight the relay to be programmed and press the

SELECT button. This action will bring up the List of Alarms/Faults screen. (Figure 80). Initially, the

box beneath the relay will be empty.
To attach an alarm to each relay, follow the steps under Navigating Protocol on page 56.

Figure 80 List of alarm faults screen

The alarm at the top of the screen will be flashing.

NOTE
Alarms have a separately programmable function that allows them to be latching or non-

latching. If the alarm is latched, then the programmable relay will also latch until the alarm is

reset.

!

CAUTION

Navigating through screens with additional navigational selections at the bottom of the

display screen is slightly different from navigation involving only the navigation buttons

below the display screen. Specific instruction is given below.

NOTE
If the Npower has Open Comms-Discrete Inputs (Input Contact Isolators, Section 7 of the

Options Manual, these will show up on the alarm list and can be selected to connect to a

programmable output relay.

PROGRAMMABLE OUTPUT RELAY BOARD # 1

SAVE & EXIT

PROGRAMMABLE RELAY # 1

PROGRAMMABLE RELAY # 2

PROGRAMMABLE RELAY # 3

PROGRAMMABLE RELAY #4

PROGRAMMABLE RELAY #5

PROGRAMMABLE RELAY #6

PROGRAMMABLE RELAY #7

PROGRAMMABLE RELAY #8

CANCEL

RELAY ASSIGNMENTS...........................USER DEFINED

ALARM / FAULT NAME

EXIT

BATT. FUSE FAIL

BATT. LOW XFER

DC OV TRANSIENT

INP PHASE ROT ERROR

RECT. FUSE FAIL

RECT DRIVE 1 FAIL

PROG RELAY # 1

BATTERY FUSE FAIL

CLEAR

REMOVE

ADD

DOWN

UP