Philips T-SMART DBS-EX23-530 User Manual

Page 76

Advertising
background image

Alarm Settings

Programming Reference

4-24

DBS-EX23-530

Revised April 2000

Parameter

Loss of Signal Counter

Description

Determines how many instances of loss of signal occur before a
Signal Loss FF key is lit.

The FF key lights when the counter exceeds the specified number
within a 24-hour period.

(See page 4-35 for instructions on programming ISDN FF keys.)

Programming

Master cabinet: FF1 9# 4# 4# 3# 4# (0-9000)#

Slave cabinet: FF1 9# 4# 5# 3# 4# (0-9000)#

Options

0-9000

/

24 hours

(9000)

Parameter

Sync Loss Counter

Description

Determines how many instances of sync loss occur before a Sync
Loss FF key is lit.

The FF key lights when the counter exceeds the specified number
within a 24-hour period.

(See page 4-35 for instructions on programming FF alarm keys.)

Programming

Master cabinet: FF1 9# 4# 4# 3# 5# (0-9000)#

Slave cabinet: FF1 9# 4# 5# 3# 5# (0-9000)#

Options

0-9000

/

24 hours (9000)

Parameter

Yellow Alarm Counter

Description

Determines how many yellow alarm indications occur before a
Yellow Alarm FF key is lit.

The FF key lights activated when the counter exceeds the specified
number within a 24-hour period.

(See page 4-35 for instructions on programming FF alarm keys.)

Programming

Master cabinet: FF1 9# 4# 4# 3# 6# (0-9000)#

Slave cabinet: FF1 9# 4# 5# 3# 6# (0-9000)#

Options

0-9000/24 hours (9000)