background image

DeviceNet Physical Layer and Media

Adept SmartController User’s Guide, Rev. E

119

The baud rate of the system depends on the length of the network (end-to-end) and the
type of cable.

Table B-3

shows how cable selection and trunkline length affect the

maximum data rate on the network.

Figure B-2

shows a thick cable, and

Figure B-3

, a thin

cable.

Table B-2. Features of a DeviceNet Network

Network Size

A maximum of 64 nodes [0...63]

Network Length

Selectable, end-to-end network distance varies with speed

Baud Rate

Distance (thick cable)

125 Kbps

500 m (1,640 ft.)

250 Kbps

250 m (820 ft.)

500 Kbps

100 m (328 ft.)

Data Packets

0-8 bytes

Bus Topology

Linear (trunkline/dropline); power and signal on the same
network cable

Bus Addressing

Multi-Master and Master/Slave special case; polled

System Features

Removal and replacement of devices from the network under
power not supported by Adept

Table B-3. DeviceNet Data Rates Relative to Cable Type and Length

Data Rates

125 Kbps

250 Kbps

500 Kbps

Thick Trunk Length

500 m
(1,640 ft.)

250 m
(820 ft.)

100 m
(328 ft.)

Thin Trunk Length

100 m
(328 ft.)

100 m
(328 ft.)

100 m
(328 ft.)

Maximum Drop Length

6 m
(20 ft.)

6 m
(20 ft.)

6 m
(20 ft.)

Cumulative Drop Length

156 m
(512 ft.)

78 m
(256 ft.)

39 m
(128 ft.)