Manual Control Pendant Basics

Adept SmartController User’s Guide, Rev. E

127

MCP-4 Compatibility

The MCP-4 has a dual-channel (four-wire) E-Stop circuit where the switch contacts are in
parallel. This is different from the MCP III where the switch contacts are in series. This
difference affects how the MCP-4 is used in various Adept systems.

Table C-1

covers the

compatibility status for the MCP-4.

Table C-1. MCP-4 Compatibility Guidelines

In Adept systems rated for Category 1 Safety

In MV Controller-based
systems with CIP2, CIP1, or
VFP

MCP-4 is compatible, no issues

In SmartController-based
systems

In systems that are shipped from the factory with an MCP-4, there are
no compatibility issues.

If you are installing an MCP-4 in a system that originally used an MCP
III, then Adept recommends removing 10356-10370, CIM TO MCPIII
Adapter for reliability, but not for compliance reasons.

In Adept systems rated for Category 3 Safety (CE: Redundant Channel, RIA: Control Reliable)

In MV Controller-based
systems with CIP2 or CIP1

To maintain a dual contact enable in CE Category 3 Emergency Stop
systems, remove jumper JP3 inside CIP.

In MV Controller-based
systems with VFP3

MCP-4 not compatible. Cannot maintain a dual contact enable with the
MCP-4, must use MCP III.

In SmartController-based
systems

In systems that are shipped from the factory with an MCP-4, there are
no compatibility issues.

If you are installing an MCP-4 in a system that originally used an MCP
III, then you must remove 10356-10370, CIM TO MCPIII Adapter. This
must be done for compliance reasons in order to maintain a dual
contact enable in CE Category 3 Emergency Stop systems.