Freedom SW 3000 Owner’s Guide

Configuration

You can adjust the power share settings as follows:

When to use

Set the Power Share setting to match the AC input breaker.

Use this setting when connecting to an AC source. If using multiple AC
sources via an AC transfer switch, adjust this setting to the smaller AC
breaker size.

Outcome

Setting the value higher than the AC source’s external breaker

could cause the external breaker to trip.

Equalize

Configurable setting

This setting lets you enable or disable charger

equalization, if the battery type is flooded (or wet). Equalization can be
turned on (enabled) or off (disabled). The default setting for equalize is Off.

When to use

Review the section, “Operating in Equalization Mode” on

page 10 before adjusting this setting. This menu item is displayed if the
battery type allows equalization.

In the Freedom SW 3000 home menu, highlight Equalize, as shown in
Figure 21.

When you select On, the equalization confirmation warning appears, as
shown in Figure 22.

Range of values

Increment

Default

5 to 30 amps

5 amps

30 amps

Equalize

[Off]

Figure 21 Equalize On

[Enabled]

[10.0A]

[On]