Troubleshooting

Table 9

provides a detailed description of the fault messages and solutions. If you are unable to resolve the problem after referring to this table, contact

your dealer or Customer Service.

Table 9 Fault Messages

Fault
Number

Message

Fault Type

Cause

Solution

F0

Unit is too hot and has shut
down. See guide.

Automatic

FET1 Over Temperature
Shutdown

Clear the fault and attempt restart. Ensure
adequate ventilation around the Freedom
SW 3000. Reduce AC loads.

F2

Unit is too hot and has shut
down. See guide.

Automatic

FET2 Over Temperature
Shutdown

Clear the fault and attempt restart. Ensure
adequate ventilation around the Freedom
SW 3000. Reduce AC loads.

F3

Unit is too hot and has shut
down. See guide.

Automatic Transformer

Over

Temperature Shutdown

Clear the fault and attempt restart. Ensure
adequate ventilation around the Freedom
SW 3000. Reduce AC loads.

F4

Battery over-temp. Inv/Chg
has shut down. See guide.

Automatic

Battery Over Temperature
Shutdown

Clear the fault and attempt restart. Stop
charging, check battery voltage and
temperature. Check for excessive ambient
temperature and adequate ventilation in
the battery compartment.

F5

is too hot and has shut
down. See guide.

Automatic

Ambient Over Temperature
Shutdown

Clear the fault and attempt restart. Ensure
adequate ventilation around Freedom SW
3000. Reduce AC loads.