Configure Inv/Chg Menu

Cfg/Inv Chg is a sub-menu. If selected, the following list of sub-menu items
appears.

Max Chg Rate

Full name

Maximum charge rate

Configurable setting

The actual battery charge rate is determined by two

things: the battery bank size setting (C) divided by 5 (C÷5) and the charge
rate setting (0 to 100%).

For example, if the battery bank size is set to 300 Ah (C) and the charge rate
is set at 100%, the maximum charge rate is:

300 ÷ 5 = 60 amps × 100% which is a 60 amp charge rate.

If the charge rate setting is adjusted to 50%, the maximum charge rate is:

300 ÷ 5 = 60 amps × 50% which is a 30 amp charge rate.

The Freedom SW 3000 has a maximum charge rate of 150 amps. Even
though you can set a bank size of 2000 Ah, where C÷5 is 2000 ÷5 = 400
amps, the Freedom SW 3000 would still charge at 150 amp maximum.

You can adjust the Max Chg Rate settings as follows:

When to use

Displayed only if in charger mode when you wish to control

the maximum charge rate to your batteries.

Lo DC Volt

Full name

Low DC input voltage shutdown

Configurable setting

This setting lets you set the low voltage shutdown

level for the inverter.

You can adjust the Lo DC Volt settings as follows:

When to use

This setting limits the depth of discharge on your battery.

Batt Type

This feature is the same as described on the basic menu on page 37.

Batt Size

This feature is the same as described on the basic menu on page 37.

Max Chg Rate

[100%]

Range of values

Increment

Default

10% to 100%

10

100%

Lo DC Volt

[10.0V]

Range

Increment

Default

10 to 12 volts

0.1 volt

10 volts