Troubleshooting

F6

Too many AC loads. Turn
some off, clear fault, try
again.

Escalating Auto Fault.
Must occur 3 times in 30
seconds before becoming a
manual fault.

AC Overload Shutdown
(AC OUTPUT)

Clear the fault and attempt restart. Reduce
AC loads.
Check that AC input wiring is not
connected to the AC output.

F9

Battery voltage is too high.
See guide.

Automatic

DC Over Voltage
Shutdown

Clear the fault and attempt restart. Ensure
battery voltage is 10–16 VDC at Freedom
SW 3000 terminals. Check all other
charging source outputs, battery cables.

F10

Battery is too low, can’t
invert. Recharge battery.

Automatic

DC Under Voltage
Shutdown (Immediate)
occurs if DC voltage is
below 8 volts DC

Clear the fault and attempt restart.
Recharge batteries. Check battery cable
connections.

F11

Battery is too low, can’t
invert. Recharge battery.

Automatic

DC Under Voltage
Shutdown occurs if DC
voltage is below 10 volts
DC.

Clear the fault and attempt restart.
Recharge batteries. Check battery cable
connections.

F23

Inverter/Charger internal
failure. Service required.

Escalating Auto Fault.
Must occur 3 times in 30
seconds before becoming a
manual fault.

AC Over Voltage
Shutdown (Inverter AC
output)

Service required.

Table 9 Fault Messages

Fault
Number

Message

Fault Type

Cause

Solution