Stack dryer foundation specifications, Specifications – Grain Systems PNEG-1717 User Manual

Page 28

Advertising
background image

4. Specifications

28

PNEG-1717 CE Approved GSI/FFI Portable Dryer Manual

Stack Dryer Foundation Specifications

Minimum soil bearing capacity = 2000 PSF.

Concrete specifications:

Compressive strength at 28 days - 4000 PSI.

Minimum cement content - 6 sacks/yard.

Maximum slump - 4"±1".

Stack Dryer Foundation

Basket Length

14

18

20

22

26

Concrete Pad Size (12' x “X”)

1

12' (3657.6) x

24' (7315.2)

12' (3657.6) x

28' (8534.4)

12' (3657.6) x

30' (9144.0)

12' (3657.6) x

32' (9753.6)

12' (3657.6) x

36' (10972.8)

Concrete (Cubic Yards) (Cubic Meters)

20-3/4

(15.86451)

24-1/4

(18.54046)

26

(19.87843)

27-1/2

(21.02526)

31

(23.7012)

#4 Rebar (Feet)

2

(mm)

900'

(274320)

1060'

(323088)

1140'

(347472)

1220'

(371856)

1400'

(426720)

Anchors

3

16

20

22

24

28

1

10" (254 mm) Depth with 36" (914.4 mm) wide x 36" (914.4 mm) deep footings along each side.

2

#4 Reinforcing rods on 1' (304.8 mm)-0" centers. Both directions in slab and bottom of footing.

3

Use 3/4" (19.05 mm) x 9-5/8" (244.475 mm) minimum anchors with epoxy. GSI part #: Anchor (GTC-0003)

epoxy (GTC-0004).