8. Vision/Dri-Tek Dryer Operation

42

PNEG-1717 CE Approved GSI/FFI Portable Dryer Manual

Figure 8I

Figure 8J

9. Calibrate the moisture sensors, taking the average of at least three (3) samples both incoming (moist)

and outgoing (dry).

Step 17 on Page 38

, SETUP > M/C Setup > CALIBRATE SENSORS > enter

offset > ACCEPT.

(See Figure 8K on Page 43.)

Example: Reading = 18.3%, Sample = 17%,

Offset = -1.3%. The moisture tester gives an average moisture of 17%, but the moisture sensor on
the dryer reads 18.3%.