Appendix B - Profibus

B.5. Setting Parameters Registers for Data Request

Parameter

#

Range

Default

Main Parameters

Starter Current

0

8..1400

58 (Amp.)

Motor Current

1

4..1750

58 (Amp.)

Line/Delta Configuration

2

0 (Line), 1 (Inside Delta)

0 (Line)

Undercurrent_FLT

3

0..90 (% of FLA)

0 (% of FLA)

Undercurrent_DLY 4

1..40

10

(Seconds)

O/C JAM Fault

5

200..850 (% of FLA)

850 (% of FLA)

O/C JAM Delay

6

0..50

5 (0.5 Sec.)

Overload_Class

7

75..150

115 (% of FLA)

Overload_Protect 8

1..10

4

(Seconds)

Undervoltage_FLT 9

120..600

300

(Volt)

UnderVoltage_DLY 10

1..10

5

(Seconds)

Overvoltage_FLT 11

150..750

480

(Volt)

Overvoltage_DLY 12

1..10

2

(Seconds)

Reserved 14..23

Start Settings

Soft Start Curve

24

0..10 (5..9 are reserved)

0 (Standard).

Kickstart Time

25

0..10 (Tenth Seconds)

0 (No Pulse)

Starting Voltage/Current

26

10..80

30 (% of full
voltage)

Current Limit

27

100..500

400 (% of FLA)

Ramp UP Time

28

1..90

10 (Seconds)

Max. Start Time

29

1..250

30 (Seconds)

Number of Starts

30

1..10 & (11 = OFF)

10

Duty Cycle Time

31

1..60

30 (Minutes)

Start_Lockout 32

1..60

15

(Minutes)

EOR Relay Delay

33

0..40

5 (Seconds)

Reserved 35..39

Stop Settings

Soft Stop Curve

40

0..10 (5..9 are reserved)

0 (Standard)

Ramp DOWN Time

41

1..30

10 (Seconds)

End Torque

42

0..10

0 (Minimum)

Reserved 43..47

Dual Settings

Starting VOLT-2

48

10..80 % of full voltage

30

Current Limit-2

49

100..500

400 % of FLA

Ramp UP-2

50

1..90

10 (Seconds)

Ramp DOWN-2

51

1..30

10 (Seconds)

Motor Current-2

52

5..1400

31 (Amp.)

Reserved 53..55

Slow SP & Saving Parameters

Energy Saving

56

1..10

0

Slow Sp eed TRQ.

57

1..10

8

Max_Slow_SP_Time 58

1..250

30

(Seconds)

Reserved 59..62

Fault Settings

Phase Loss

63

0..1

0 (No)

Phase Sequence

64

0..1

0 (No)

Auto Reset

65

0 / 1 (0 - No, 1 - Yes)

1 (No)