16 operating via communication links – GE Industrial Solutions ASTAT XT User Manual

Page 70

Advertising
background image

70

• Application diagrams

8.16

Operating via Communication Links

Notes:

•

In order to operate via communication, either Modbus (standard) or Profibus (optional) or DeviceNet

(optional) optional PCBs must be installed and wired properly.

•

ASTAT-XT must be properly grounded.

•

ASTAT-XT must be programmed to enable control (not only monitoring). Refer to section

4.7.9 and

4.7.10 page 42 for programming.

•

Make sure that after programming, Control Supply voltage is disconnected and reconnected so that

the communication settings will take affect.

•

ASTAT-XT will toggle between communication commands and local commands UNLESS switches A or

B are opened.

o

Switch A and B each overrides a START command coming from the communication channel.

o

Switch A can be used as an immediate stop that prevents an unwanted remote start coming
from communication.

o

Switch C can be used as a local SOFT START.

o

Switch B can be used as a local SOFT STOP.

WARNING

Beware!
ASTAT-XT must be grounded at all times.
When testing the ASTAT-XT control/communication it is possible to use the control
module only without the power section (ASTAT-XT 85A and up).
The control module MUST be properly grounded to avoid danger of electrical shock!!