Appendix A - MODBUS RTU Protocol

Parameter

#

Range

Default


Slow SP & Saving Parameters
Energy Saving

57

0..10

10 ( Max Save)

Slow

Speed_TRQ.

58

1..10

8

Max_Slow_SP_Time

59

1..60

30

(Seconds)

Reserved

60..63


Fault Settings
Phase

Loss

64

0..1

(0-Disabled,

1-Enabled)

1

(Enabled)

Phase Sequence

65

0..1 (0-Disabled, 1-Enabled)

0 (Disabled)

Auto Reset

66

0 / 1 (0-Disabled, 1-Enabled)

0 (Disabled)

Thermistor Type

67

0 / 1 (0 - PTC, 1 - NTC)

0 (PTC)

Thermistor Trip

68

0..100 Tenth Kohm 0.1..10 K

0 (Disabled)

Undercurrent RST

69

10..120 (&121=Disabled)

121 (Disabled)

Reserved

70-72


I/O Settings
PROG. Input # 7

73

0..2 (0=En.Save,1=S.Spd,2=Rst)

0 (Reset)

PROG. Input # 8

74

0..2 (0=D.Set.,1=Rvrs,2=Rst)

0 (Dual Set)

PROG. Fault Relay

75

0..1 (0=Fault close, 1=Fault open)

0 (Fault close)

Relay

ON

Delay 76

0..3600

0

(Seconds)

Realy

OFF

Delay 77

0..3660

0

(Seconds)

Analog

Output

78

0-

Current,

0..200% of motor_fla

0- Current

Reserved

79..80


COMM. Parameters
COMM.

Protocol 81

0-Modbus,1-Profibus,

2-DeviceNet

0-Modbus

Baud Rate

82

12..96 (*100) Auto for Profibus

96 (9600 bps)

Parity Check

83

0/1/2 (Even / Odd / No)

0 (Even)

Station Number

84

1..247 & (248= Off)

248 (Off)

1..126

&

(127=

Off)

for

Profibus

S.

Link

Par.

Set

85

0

(Disable),

1

(Enable)

0

(Disable)

S.

Link

Control

86

0

(Disable),

1

(Enable)

0

(Disable)

Reserved

87…89

Modbus_#_Array

90..109 (# of parameter)

(defaults # are:

1 - Logic Status, 2 - I, 3 - V, 5 – Control In, 11 – Thermistor

Resistance, 37 – Thermal Capacity, 10 – frequency,

4 - Phase

Sequence, 6-Dip Switch, 18 – Total Run Time,

19 – Total Starts, 20-Last Start Period, 21-Last Start Peak I,

22-time to start, 23 – Total Trips, 24-last trip Number, 25 – Pre Trip I,

26 – Time to Reset U/C, 39-Spare, 40-Spare


Notes:

1. Parameter # is "1 based". The address is 1 lower than parameter #. For example address of parameter #1 is

0 (40000).

2. When the Preset Single Register Function (06) is used to adjust one parameter setting, the communication

program checks that the parameter value is within the allowed limits. If not, an Exception Response
(Exception code 03) is returned instead of Normal response. See Exception Responses later in this document.

3. If Preset Multiple Register Function (16) is used to adjust one or multiple parameter settings, then even if one

or more parameter settings are out of range, Normal response will be returned.
ASTAT-XT program will check later the value of each parameter. If it is beyond the allowed limit, the limit
value will be stored instead of the transmitted parameter value.

4. It is strongly recommended to preset parameter settings only when the motor is stopped. The ASTAT-XT

enables, however to preset one parameter (using function 06 only) when the motor is running at full voltage.
When motor is Soft Started, Soft Stopped, runs with energy saving or at slow speed, the ASTAT-XT ignores
"Preset Single Register" or "Force Multiple Register" instructions. A "busy" Exception response is returned by
ASTAT-XT whenever its logic condition does not enable presetting.