Appendix A - MODBUS RTU Protocol

Example 9:

To read all discrete inputs of ASTAT-XT # 12, the host computer sends the following Query frame:

byte 1: Serial Link No.

($0C) (12)

byte 2: Function

($02)

byte 3: Starting Address High ($00)
byte 4: Starting Address Low ($00)
byte 5: No. of Points High

($00)

byte 6: No. of points Low

$08)

byte 7: CRC_Low

($XX)

byte 8: CRC_High

($XX)


The ASTAT-XT response when only Stop and Soft Stop terminals (Inputs 1&2) are connected:

byte 1: Serial Link No.

($0C)

(12)

byte 2: Function

($02)

byte 3: Byte Count

($01)

byte 4: Data (Inputs 7..0)

($03)

byte 5: CRC_Low

($XX)

byte 6: CRC_High

($XX)


A.12. Diagnostics

Modbus Function 08 as implemented in the ASTAT-XT supports only Subfunction $0000. It provides for the
"loopback" (Return Query Data) feature, and for checking the Communication Serial Link between the master and
the ASTAT-XT.
To request ASTAT-XT # 1 to return Query data, the master should send following Query frame:

byte 1: Serial Link No.

($01)

byte 2: Function

($08)

byte 3: Subfunction High

($00)

byte 4: Subfunction Low

($00)

byte 5: Data High

($37)

byte 6: Data Low

($A5)

byte 7: CRC_Low

($XX)

byte 8: CRC_High

($XX)


The Normal (if no exception) response is the echo of the Query:

byte 1: Serial Link No.

($01)

byte 2: Function

($08)

byte 3: Subfunction High

($00)

byte 4: Subfunction Low

($00)

byte 5: Force Data High

($37)

byte 6: Force Data Low

($A5)

byte 7: CRC_Low

($XX)

byte 8: CRC_High

($XX)