1 soft start parameters – GE Industrial Solutions ASTAT XT User Manual

Page 32

Advertising
background image

32

• Control Keypad

Function &

Default

Range

Unit

Description

Max. Start Time
30 SEC.

1-60

sec.

Sets Maximum Start Time
The maximum allowable start time, from the start signal to the
end of the acceleration process. If voltage/speed does not reach
nominal during Max. Start Time then ASTAT-XT will trip the
motor and create a fault. The LCD will display the Long Start
Time

fault message.

For example, this can occur when the Current Limit setting
is too low.
Notes:

When Overload Class is set to NEMA Class 10 Max.

Start Time

can be set to 15 seconds maximum.

When Overload Class is set to IEC Class 10 or NEMA

Class 20

Max. Start Time can be set to 30 seconds

maximum.

When Overload Class is set to IEC Class 20 or NEMA

Class 30 Max. Start Time

can be set to 60 seconds

maximum with limitation automatically calculated by the soft
starter.

Number of Starts
10

1-10, OFF

Sets Number of Starts permitted during Duty Cycle Time (see
below).
Limits the Number of Starts during the period of time
defined by Duty Cycle Time.
If you try to start even one more time within that period the
START Lockout

period will take effect.

Duty Cycle Time
30 Min.

1–60

min.

Sets Duty Cycle Time during which Number of Starts is counted.
During the START Lockout period the Wait before RST
XX Min

message will be displayed.

Start Lockout
15 Min.

1–60

min.

Sets START Lockout time during which starting is disabled after
Too Many Starts

trip.

EOR Relay Delay
5 Sec.

0-120

sec.

Sets the time delay for the End of Ramp relay to close.
End of Ramp relay can signal that the motor is at its full speed
which can be used for closing the bypass contactor and for
loading the motor.

Store Settings
Start Settings

Same

as

Store Settings Main Settings

on page 28.


4.7.3.1

Soft Start Parameters

The ASTAT-XT incorporates five starting curves to enable you to select a suitable torque curve.

Soft Start Curve 0

– Standard curve (Default). This curve is the most suitable curve for preventing prolonged

starting and motor overheating.

Note:
When ASTAT-XT is connected in DELTA Conf., the ASTAT-XT will always use Curve 0 regardless of the curve
defined.