• Control Keypad

4.7.8

I/O Settings Parameters

41

– Page 7

Function &

Default

Range

Unit

Description

PROG. Input # 7
Reset

Reset;
Slow Speed;
Energy Saving

Sets the terminal 7 function
Refer to section

4.7.8.1 on page 41.

PROG. Input # 8
Dual Settings

Dual Settings;
Slow SPD
Reverse;
Reset;

Sets the terminal 8 function
Refer to section

4.7.8.1 on page 41.

PROG. Fault Relay
At Fault Close

At Fault Close,
At Fault Open

Sets the Fault Relay mode of operation.
When configured to At Fault Close the internal
relay is energized upon fault.

When configured to At Fault Open the relay is de-
energized upon fault. In this mode, while normal
operation, the fault relay is energized.
Relay will also de-energize upon control power outage.

Relay ON Delay
0 SEC.

0 – 3600

sec.

Sets ASTAT-XT’s Immediate Relay (RUN relay)
ON delay time.

Relay OFF Delay
0 SEC.

0 – 3600

sec.

Sets ASTAT-XT’s Immediate Relay (RUN relay) OFF delay
time.

Analog Output
I, 0...200% OF Im

I, 0...200% OF Im

Sets Analog Output mode of operation.
The dip switch settings on the analog card define full
scale as either 20mA or 10V. Refer to section

5.7 on

page 51 for more details.
The full scale of the analog card is related to 200% of
Motor Current

(2x <rated motor current>).

Store Settings
I/O Settings

Same

as

Store Settings Main Settings

on

page 28.


41

Displays in MINIMIZED MODE and MAXIMIZED MODE.