GE Industrial Solutions ASTAT XT User Manual

Page 112

Advertising
background image

112

Appendix C - DeviceNet™ to Modbus™ Gateway

Code Class

Level Instance

Level

0E

HEX

Yes Yes Get_Attribute_Single

10

HEX

No

Yes

Set_Attribute_Single

C.5. Assembly Object (04

HEX

– 4 Instances)

C.5.1.

Class Attributes (Instance 0)

Attribute
ID

Name DeviceNet

Data Type

Data
Value

Access Rule

1 Revision

UINT 2 Get

2 Max

Instance

UINT 112

Get

100 Input

Index

60 = Instance 60
61 = Instance 61
100 = Instance 100

USINT

2

Get / Set

48

101

Input Size (in bytes)

UINT

1

Get

102 Output

Index

112 = Instance 112

USINT

0

Get / Set

49

103

Output Size (in bytes)

UINT

1

Get

C.5.2.

Output (O2T) Instance Attributes – Register 40752

Attribute
ID

Name DeviceNet

Data Type

Data
Value

Access Rule

3 Output

Data

USINT[]

0

Get/Set

C.5.2.1.

Output Instance 112 (0x70) – Control Output

Byte Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2 Bit 1

Bit 0

0

Reset

Slow Speed
Reverse

Slow
Speed

Dual
Adjust

Energy
Save

Start Soft Stop Stop

C.5.3.

Input (T20) Instance Attributes – Register 40257

Attribute
ID

Name DeviceNet

Data Type

Data
Value

Access Rule

3

Input Data

USINT[]

0

Get

C.5.3.1.

Input Instance 60 (0x3C) – Basic Softstart Input

Byte Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

At
Reference

Reserved Reserved Reserved Reserved

Running
1

Reserved

Faulted /
Trip

C.5.3.2.

Input Instance 61 (0x3D) – Extended Softstart Input

Byte Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

At
Reference

Reserved

Control
From Net

Ready Running2 Running1 Warning

Faulted /
Trip

C.5.3.3.

Input Instance 100 (0x64) – Status

Byte Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Slow
Speed
Reverse

Reserved Reserved Reserved Reserved Reserved

Reserved

Reserved

1

ASTAT-XT
Tripped

Stopped

Soft Stop
Process

Start
Process

Running

Dual_Adjust
On

Energy
Save On

Slow
Speed

48 Stored to NVRAM
49 Stored to NVRAM

Advertising