• Application diagrams

8.15

Reversing with Two Line Contactors

Notes:

•

A N.O. auxiliary contact in each of the two line contactors C1 & C2 controls the START/STOP command.

Closure of either contactor will supply main power and a start signal to the ASTAT-XT.

•

It is recommended to employ a mechanical interlock between the forward and reverse contactors.

•

It is required to delay the transfer between opening of one contactor and closing of second contactor.

•

Phase Sequence

fault must be disabled to operate reversing contactors at the line input of the

ASTAT-XT. Refer section

4.7.7 page 38 for programming.