• Technical Specifications

Terminal Function

Description

Terminal SG

No connection

Standard RS485, half duplex with Modbus protocol, baud

rate 1200, 2400, 4800, 9600 BPS.

Terminal D-

RS-485 communication (-)

Twisted shielded pair should be used.

Connect shield to ground on the PLC/Computer side.

Terminal D+

RS-485 communication (+)

Terminals 4 & 5 must be wired to Control Supply for

operation in communication mode (refer to section

8.16

page 70 for wiring diagram).

Up 32 units can be connected for Modbus RS485

communication. For reliable communication, units should
be installed in the vicinity of 200m maximum, from the first
to the last unit.

Refer to section

4.7.9 page 42 for programming.

Refer to Appendix A of this manual for Modbus protocol

manual.

Terminal 28

Thermistor input (T1)

Thermistor input is programmable as a PTC or NTC type
thermistor. The trip value is adjustable between 1-10Kohm,
preset delay of 2 Sec.

Terminal 29

Thermistor input (T2)

Connect thermistor and/or Analog output shield to ground
terminal.

Terminal 30

Ground

Analog output (0-10VDC or 0-20mA or 4-20mA)

Terminal 31

Analog output (-)

Reflects motor current and is related to 2xIm. i.e., Full scale
(10VDC or 20mA) is related to 2xIm.

Terminal 32

Analog output (+)

Note:
Refer to section

5.7 page 51 for analog output PCB dip switch

setting.

Refer to section

4.7.8 page 40 for Analog Output

programming.

Refer to section

4.7.7 page 38 for Thermistor Type and

Thermistor Trip

programming.

D-9 connector Profibus communication

(optional)

Profibus DPV0 and DPV1, up to 12 MBPS.

D type 9 pin connector is applied.

Control, monitoring and setting parameters can be achieved

via the Profibus connection.

Setting is possible only when DPV1 is implemented.

Refer to section

4.7.10 page 42 for programming.

Refer to Appendix B of this manual for Profibus protocol

manual.

Terminal V-

0 Volt external power supply

Terminal CL

Negative data line

Terminal Dr

Cable shield

Terminal CH

Positive data line

Terminal V+

DeviceNet communication
(optional)

+24V external power supply

Advertising