GE Industrial Solutions ASTAT XT User Manual

Page 16

Advertising
background image

16

• Technical Specifications

Terminal Function

Description

Terminal SG

No connection

•

Standard RS485, half duplex with Modbus protocol, baud

rate 1200, 2400, 4800, 9600 BPS.

Terminal D-

RS-485 communication (-)

•

Twisted shielded pair should be used.

Connect shield to ground on the PLC/Computer side.

Terminal D+

RS-485 communication (+)

•

Terminals 4 & 5 must be wired to Control Supply for

operation in communication mode (refer to section

8.16

page 70 for wiring diagram).

•

Up 32 units can be connected for Modbus RS485

communication. For reliable communication, units should
be installed in the vicinity of 200m maximum, from the first
to the last unit.

•

Refer to section

4.7.9 page 42 for programming.

•

Refer to Appendix A of this manual for Modbus protocol

manual.

Terminal 28

Thermistor input (T1)

Thermistor input is programmable as a PTC or NTC type
thermistor. The trip value is adjustable between 1-10Kohm,
preset delay of 2 Sec.

Terminal 29

Thermistor input (T2)

Connect thermistor and/or Analog output shield to ground
terminal.

Terminal 30

Ground

Analog output (0-10VDC or 0-20mA or 4-20mA)

Terminal 31

Analog output (-)

Reflects motor current and is related to 2xIm. i.e., Full scale
(10VDC or 20mA) is related to 2xIm.

Terminal 32

Analog output (+)

Note:
Refer to section

5.7 page 51 for analog output PCB dip switch

setting.

•

Refer to section

4.7.8 page 40 for Analog Output

programming.

•

Refer to section

4.7.7 page 38 for Thermistor Type and

Thermistor Trip

programming.

D-9 connector Profibus communication

(optional)

•

Profibus DPV0 and DPV1, up to 12 MBPS.

•

D type 9 pin connector is applied.

•

Control, monitoring and setting parameters can be achieved

via the Profibus connection.

•

Setting is possible only when DPV1 is implemented.

•

Refer to section

4.7.10 page 42 for programming.

•

Refer to Appendix B of this manual for Profibus protocol

manual.

Terminal V-

0 Volt external power supply

Terminal CL

Negative data line

Terminal Dr

Cable shield

Terminal CH

Positive data line

Terminal V+

DeviceNet communication
(optional)

+24V external power supply

Advertising