49

• Installation

ASTAT-XT main PCB.

Dip switches location, software version label location and PCB hardware version identification.



5.5

Dip Switch Settings on the Main PCB

The dip switch has eight separate switches. It is located under the front cover of the control module (models
QTx0085x-QTx1400) or under the display unit (models QTx0008x-QTx0072).

No.

Switch Function

Switch Off

Switch On

1 Display

format

Minimized

Maximized

2 Not

Used

-

-

3 Mains/generator

Mains

Generator

4 Must

be

OFF

-

-

5

LCD language selection

See tables below section

5.5.4 page 50.

6

7

Expanded settings

Disabled

Enabled

8 Software

lock

Open

Locked


5.5.1

Switch # 1 – Display Modes

Two display modes are available:
Maximized – display of all possible parameters.
Minimized – display of pre-selected parameters.
Setting switch # 1 to OFF will minimize the LCD displays.
Refer also to section

4.6 page 23.

Maximized Mode - Switch #1 – On

Minimized Mode Switch #1 – Off

Display Only
Main Settings
Start Settings
Stop Settings
Dual Settings
Slow SP & Saving Parameters
Fault Settings
I/O Settings Parameters
COMM. Parameters
Statistical Data

Display Only
Main Settings
Start Settings
Stop Settings
Statistical Data