Appendix C - DeviceNet™ to Modbus™ Gateway

C.11.3.

Common Services

Implemented for

Service
Code

Class Level

Instance Level

Service Name

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set

Attribute

Single

C.12. Start Settings Object (72

HEX –

1 Instance)

C.12.1.

Class Attributes (Instance 0)

Attribute
ID

Name DeviceNet

Data Type

Data Value

Access
Rule

1 Revision

UINT

1 Get

C.12.2.

Instance Attributes (Instance 1)

Attribute
ID

Name Range

Default
Value

Access
Rule

Modbus
Address

1 Soft

Start

Curve

0-10 0

Get/Set

40025

2

Kickstart Time

0-10 (10

th

Sec)

0

Get/Set

40026

3 Starting

Voltage/Current

10-80 30

Get/Set

40027

4 Current

Limit

100-500

400

Get/Set

40028

5

Ramp UP Time

1-90

10

Get/Set

40029

6 Max.

Start

Time

1-250 30

Get/Set

40030

7

Number of Starts

1-10 & 11 - OFF 10

Get/Set

40031

8

Duty Cycle Time

1-60

30

Get/Set

40032

9 Start_Lockout

1-60 15

Get/Set

40033

10

EOR Relay Delay

0-40

5

Get/Set

40034

C.12.3.

Common Services

Implemented for

Service
Code

Class Level

Instance Level

Service Name

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set

Attribute

Single

C.13. Stop Settings Object (73

HEX –

1 Instance)

C.13.1.

Class Attributes (Instance 0)

Attribute
ID

Name DeviceNet

Data Type

Data Value

Access
Rule

1 Revision

UINT

1 Get

C.13.2.

Instance Attributes (Instance 1)

Attribute
ID

Name Range

Default
Value

Access
Rule

Modbus
Address

1 Soft

Stop

Curve

0-10

0

Get/Set

40041

2

Ramp DOWN Time

1-30

10

Get/Set

40042

3 End

Torque 0-10

0

Get/Set

40043

C.13.3.

Common Services

Implemented for

Service
Code

Class Level

Instance Level

Service Name

0E

HEX

Yes

Yes

Get Attribute Single

10

HEX

No

Yes

Set

Attribute

Single

C.14. Dual Settings Object (74

HEX –

1 Instance)

C.14.1.

Class Attributes (Instance 0)

Attribute Name

DeviceNet Data

Value Access