Appendix C - DeviceNet™ to Modbus™ Gateway

Forward

C.5.4.

Common Services

Implemented for

Service
Code

Class Level

Instance Level

Service Name

0E

HEX

Yes Yes Get_Attribute_Single

10

HEX

Yes Yes Set_Attribute_Single

C.6. Connection Object (05

HEX –

2 Instances)

C.6.1.

Class Attributes (Instance 0)

Attribute
ID

Name DeviceNet

Data Type

Data
Value

Access Rule

1 Revision

UINT 1 Get

C.6.2.

Instance Attributes (Instances 1-2) Explicit, Polled I/O

Attribute
ID

Name DeviceNet

Data Type

Data

Value

Access
Rule

Instance

1

50

Instance

2

51

1

State

USINT

0 = NonExistent
3 = Established
5 = Deferred
Delete

0 = NonExistent
1 = Configuring
3 = Established
4 = Timed Out

Get

2 Instance

Type

USINT

0

1

Get

3 Transport

Trigger

usint 83

HEX

82

HEX

Get

4 Produced

Connection ID

uint 10xxxxxx011

BIN

xxxxxx
= Node Address

01111xxxxxx

BIN

xxxxxx
= Node Address

Get

5 Consumed

Connection ID

uint 10xxxxxx100

BIN

xxxxxx
= Node Address

10xxxxxx100

BIN

xxxxxx
= Node Address

Get

6 Initial

Comm.

Character

USINT 21

HEX

01

HEX

Get

7 Produced

Connection
Size

uint 40

4

Get

8 Consumed

Connection
Size

uint 40

4

Get

9 Expected

Packet Rate

uint

2500 msec

0

Get /
Set

12 Watchdog

Timeout Action

USINT 4

=

Deferred

Delete

0 = Timeout

Get /
Set

13 Produced

Connection
Path Length

UINT 0

3

Get

14 Produced

Connection
Path

USINT Array NULL

0x62 0x36 0x34
(0x64 = 100)

Get /
Set

52

15 Consumed

Connection
Path Length

UINT 0

0

Get

50

Instance 1 is an Explicit Message Connection.

51

Instance 2 is a Polled I/O Message Connection.

52

Must select Assembly via Connection Object per AC/DC Drive Profile (Symbolic Segment Type) – Stored in NVRAM