• Technical Specifications


3.6

Operating Modes


Operating Mode

Key

Description

Starting Voltage

1

5 to 80% Un. Adjustable via Starting Voltage parameter.

Kick Start

2

Fixed level of 80% Un with an adjustable time, 0-1 sec., via Kickstart
Time

parameter.

Acceleration Ramp

3

1-30 sec. (1-90

13

sec.). Adjustable via Ramp UP Time.

Secondary ramp 1-30sec. (1-90

13

sec.). Adjustable via Ramp UP-2

parameter.
Ramp up modes available are:
Soft Start Curve 0 (Standard)
Soft Start Curve 1!!-3!!
Soft Start Curve 4(Torque)

for linear torque control

4

Fast ramp (if the motor is up to speed before the end of normal ramp time)

Running mode

5

Nominal voltage

Soft stop mode

6

Deceleration ramp 1-30sec. (1-90

13

sec.). Adjustable via Ramp DOWN Time.

Secondary ramp 1-30sec. (1-90

13

sec.). Adjustable via Ramp DOWN-2

parameter.
Ramp down modes available are:
Soft Stop Curve 0 (Standard)
Soft Stop Curve 1!!-3!!
Soft Stop Curve 4(Torque)

for linear torque control

7

Current limiting set point (100-500%xMotor Current)

8

Acceleration ramp (continuation after motor amps drop below the current
limit).

9

Standard stopping (coast to rest)

Starting by voltage ramp:

Starting by current limitation:



13

Refer to section

5.5.5 page 50 for expanded setting.