Xylem IM157 Model MPVN User Manual

Page 4

Advertising
background image

4

• If there is any risk of injury from hot or cold machine

parts, these parts must be protected against contact by

the user, or suitable warning signs must be affixed.

• Contact protection on moving parts (e.g. Coupling

guards) must not be removed from systems that are in

operation.

• If dangerous media (e.g. explosive, toxic, hot) leak out

(e.g. from shaft seals), these must be directed away so

that there is no danger to people or the environment.

The provisions of the law must be observed.

• Measures should be taken to exclude any danger from

electricity (e.g. by complying with the local regulations

on electrical equipment). If work is carried out on

live electrical components, they should be unplugged

from the mains or the main switch turned off and fuse

unscrewed. A motor protection switch is to be provided.

• Basically, all work on the pump or pump unit should

only be carried out when the pump is stationary and

not under pressure. All parts must be allowed to return

to ambient temperature. Make sure that no one can

start the motor during such work. It is essential that

the procedure for stopping the system described in the

Operating Instructions is observed. Pumps or pump

systems that carry media that are dangerous to health

must be decontaminated before being taken apart. See

Safety Data Sheets for the various liquids handled. After

the work has been completed, all safety and protective

devices must be replaced or restarted.

Speed, Pressure, Temperature

Suitable safety measures must be taken at the plant to

ensure that the speed, pressure and temperature of the

pump and the shaft sealing do not exceed the limit values

given in the Data Sheet. The given suction pressures must

also be sufficiently high. In addition, the pump must be

protected against pressure surges such as can be caused by

switching off the plant quickly (e.g. by non-return valve on

the pressure side, flywheel, air vessel).
Permitted Forces on Flanges

Basically, the suction and pressure lines should be such that

the forces on the pump are kept to a minimum. If this is

not feasible, contact your distributor for limits.
NPSH

When entering the impeller, the liquid being handled must

have a minimum pressure NPSH to prevent cavitation or

breaking off of flow. This requirement is met if the unit

NPSH value (NPSHA) is well above the pump NPSH value

(NPSHR) under all operating conditions.
Attention must be paid to the NPSH value in particular

when liquids close to boiling point are being handled. If

the value falls below the pump NPSHR value, this can lead

to damage resulting from cavitation or serious damage

from overheating.
The NPSHR for each pump type is given in the sheets of

characteristic curves. We can supply leaflets for calculation

of NPSH values on request.
Sealing, Flushing, Cooling

Suitable facilities for the regulation and monitoring of

sealing, flushing or cooling are to be provided. When

handling dangerous liquids or if temperatures are high,

care should be taken to ensure that the pump ceases

operating if the sealing, flushing or cooling system fails.

Sealing, flushing and cooling systems must always be

operational before the pump is started up. They should

not be taken out of operation until the pump has stopped,

provided that he nature of the operation allows this at all.
Minimum Flows

If the pump is started against a closed pressure line

valve, it should be noted that the power taken up by the

pump is transmitted to the liquid handled in the form

of heat. This can cause the liquid to heat up excessively

within a relatively short time, which will then cause

damage to the pump’s internal fittings. After the pump

has reached operating speed, the discharge valve should

therefore be opened as quickly as possible. If operating

conditions mean that Q = 0 is unavoidable, or if hot

water is circulating, a free flow non-return valve, or, on

smaller systems, a by-pass pipe, should be provided. Your

distributor can help in determining the minimum flow or

designing the by-pass line.
Protection against Running Dry

The pumps must not run dry under any circumstances,

since overheating can damage pump components (e.g.

mechanical seals).
Back Flow

In systems where pumps are operating in closed circuits

under pressure (gas cushions, steam pressure), the pressure

of the gas cushion must not be reduced via the pump,

since the back flow speed may be much higher than the

operating speed, which would destroy the unit.

2. DESCRIPTION

2.1 Model

Design MPVN

Design Features:

• Vertical configuration with separate thrust bearing,

grease lubrication with grease nipples.

• Motors according NEMA-Standard MG 1-4.07.
• Flexible coupling between pump and motor.
• Medium lubricated sleeve bearing in suction casing.
• Maintenance friendly design. Shaft sealing maintainable

without pump disassembly.

Installation Position

Shaft vertical.
Other installation positions only by agreement.
2.2 Shaft Sealing

Basic design with mechanical seal. Seal code SA with

unbalanced seal; seal code SB with balanced seal.
ATTENTION: YOU WILL FIND MORE

INFORMATION ABOUT

MECHANICAL SEALS, AND THE

RISKS OF ACCIDENTS THAT THESE

MAY INVOLVE, UNDER POINT 4.6

“OPERATION AND MONITORING”

AND IN POINT 5 “MAINTENANCE

AND REPAIRS’.

2.3 Bearings and Lubrication

Drive Side: re-lubricatable roller bearings (thrust

bearing).
Pump Side: medium-lubricated sleeve bearing in the

suction casing.

Advertising