Xylem IM157 Model MPVN User Manual

Page 7

Advertising
background image

7

4.5 Starting Up

The plant may only be started up by people who

are familiar with the local safety regulations and

with these Operating Instructions (especially

with the safety regulations and safety instruction

given here).
In order to be able to observe and monitor the shaft sealing,

no protective covering is provided in this area. If the pump

is running, particular care should therefore be taken (watch

out for long hair, loose pieces of clothing etc.).
Hints for the Use as Boiler Feed Pump

Limits for cast iron when used in boiler feed or condensate

applications: pH-value 9,0 (optimum 9,3), short term:

pH-value 8,5.
The above stated values must be guaranteed at the suction

side of the pump in any case.
The water treatment must be in accordance with the

specifications for water treatment of boiler feed water in

steam plants up to 64 bar.
Air traps in the system must be avoided in any case.
Starting up for the First Time

• With MPV type pumps, no further lubrication is needed

before initial start-up.

• Pump and suction pipe must be completely exhausted

from air and filled with handling liquid before each

start up of the pump unit. When filling the pump open

screwed plug “PM2”. Close it when water is flowing out.

• Open slide valve in suction/intake pipe.
• Turn pump unit once again by hand and check that it

moves smoothly and evenly.

• Check that coupling guard is installed and that all safety

devices are operational.

• Switch on any sealing, flushing or cooling devices that are

provided. See Data Sheet for hydraulic requirements.

• Set discharge side slide valve to approx. 25% of rated

flow quantity. With pumps with a discharge branch rated

width less than 200 GPM, the slide valve can remain

closed when starting up (see also Point 1.4 “Minimum

Quantities”.

• Check direction of rotation by switching on and off

briefly. It must be the same as the directional arrow on

the bearing frame.

• Start drive device.
• As soon as it reaches normal operating speed, open

discharge valve immediately and adjust the required

operating point (see Data Sheet).

• Mechanical seals don’t need to be maintained and are

almost free of leakage.

Putting into Operation Again

(after longer standstill; 1 month)

Each time you put the pump into operation again you

have to do the same things you do when starting the pump

for the first time. The control of the rotation direction

of the unit can be dropped. You are only allowed to put

the pump into operation again automatically when the

pump remained filled with liquid during standstill and the

required test drives have been made, see point 4.7.
4.6 Operation and Monitoring

Be particularly careful not to touch hot machine

parts and when working in the unprotected

shaft seal area. Remember that automatically

controlled systems may switch themselves on

suddenly at any time. Suitable warning signs should be

affixed.
ATTENTION: REGULAR MONITORING AND

MAINTENANCE WILL EXTEND THE

LIFE OF YOUR PUMP OR PUMP

SYSTEM.
• You must observe the area of application given on the

Data Sheet.

• Do not exceed the output given on the motor rating

plate.

• Avoid dry running, running against closed discharge

valves or operation while the liquid handled is in the

vapor phase.

• Avoid sudden changes in temperature (temperature

shocks).

• The pump and motor should run evenly and without

vibrations; check at least once a week.

• Check the regulating and monitoring facilities of any

sealing, flushing or cooling systems once a week to

ensure that they function properly. Outgoing cooling

water should be body temperature.

• Pumps which are exposed to corrosive chemicals or to

wear through abrasion must be inspected periodically for

corrosion or wear and tear. The first inspection should

be carried out after six months. All further inspection

intervals should be determined on the basis of the state

of the pump.

Permitted Number of Starts

Do not exceed the pump’s permitted number of starts

– see diagram. With electric motors, the permitted number

of starts is given in the motor operating instructions. If two

different figures are given, the lower figure is valid.

4.7 Shutting Down

• Close slide valve in discharge pipe. This is not necessary

if there is a spring-loaded non-return valve.

• Switch off motor (make sure it runs down quietly.
• Close slide valve on suction side.
• Close auxiliary systems. Do not shut down cooling

system until pump has cooled down.

• If there is any risk of freezing, empty pump, cooling

system and pipes completely.

• If the pump also remains under operating conditions

(pressure and temperature) when stationary: leave all

sealing, flushing and cooling systems switched on.

• If the pump remains under operating conditions when

stationary, test drives have to be made in regular intervals

with a duration of at least 5 minutes. The intervals

Advertising