Xylem IMVS R01 Model VS Vertical Industrial Turbine Pumps User Manual

Page 7

Advertising
background image

7

DROP CABLE TEST

• Measure the resistance between the cable conduc-

tors and ground with the cable submerged in water.

See Appendix C.

4. SPLICING POWER CABLE TO MOTOR LEADS

A waterproof splice must be made to connect the

power cable to the motor leads. A properly made

splice will last the life of the pump. An improperly

made splice will become a service problem. Make the

splice per instructions supplied with the drop cable

or per instructions in the pump motor manual. The

splice should be located above the pump bowl. It

should be as compact as possible. A compact splice is

less likely to be damaged as the pump is being lowered

into the well. See Appendix B for instruction on splic-

ing the cable.

5. TESTING AFTER SPLICING POWER CABLE TO

MOTOR LEAD

Perform the following test after making the splice, but

before lowering the pump into the well.

• Check that the splice is waterproof by immersing it

in a container of water for approximately one hour

and then taking resistance readings between each

cable conductor and the water. See Appendix C.

• Measure the total resistance of the complete drop

cable and motor circuit to insure that a good splice

was made. Record the values for future reference.

THE MINIMUM READING FOR EACH

LEAD TO GROUND SHOULD BE 50

MEGOHMS.

SECTION 5 — INSTALLING THE PUMP

1. Check the pump and motor shaft to make sure it turns

free before installation. For some models, it may be

necessary to remove the suction screen in order to

check the shaft. Be sure to reinstall the suction screen.

2. Raise the bowl/motor assembly with the shipping skids

still in place. Remove the shipping skids and lower as-

sembly into the well, clamping the bowl assembly near

the top.

3. Attach the elevators to the bottom column pipe imme-

diately below the column coupling. Hoist the column

section into place above the well and the top of the

bowl assembly, providing a soft board or pipe dolly

for the end of the column pipe to slide in on so that

threads will not be damaged while the section is being

raised. Clean all threads with thread lubricant. Thread

the pipe into the discharge bowl connection and make

up tight, using one set of chain tongs for backup.

THE PUMP MOTOR WILL EXERT

A TORQUE THAT WILL TEND TO

UNSCREW THREADED COLUMN PIPE CONNEC-

TIONS. FOR THE REASON, THREADED COLUMN

JOINTS MUST BE TIGHTENED.

THE FOLLOWING TABLE GIVES THE NORMAL

AMOUNT OF THREAD ENGAGEMENT NECES-

SARY TO MAKE A TIGHT JOINT FOR THE NPT

THREAD JOINT:

Pipe

Length of

Number

Size

Thread (in.)

of Threads

3" 1"

8

4" 1

1

/

8

" 9

5" 1

1

/

4

" 10

6" 1

5

/

16

" 10

1

/

2

8" 1

7

/

16

" 11

1

/

2

10" 1

5

/

8

" 13

4. Install a cable clamp on each side of the cable splice.

See Figure 1. Be careful not to damage the cable. If

an air line is to be installed, route it beside the cable,

making sure that it is not pinched by the clamps. If

there is any danger that the splice will rub against the

well casing during installation, it should be protected

by thick rubber chaffing pads or by a steel shield.

Check that the grounding system is in place.

FAILURE TO GROUND THE UNIT

PROPERLY CAN RESULT IN SERIOUS

OR FATAL SHOCK. REFER TO ELECTRICAL CODE

REQUIREMENTS.
5. Slowly lower the unit into the well (or sump) adding

joints of column pipe as the unit is lowered. Tighten

each joint securely. See note above. Remove slack from

the power cable and attach a cable clamp approxi-

mately every 20 feet. For units with large heavy power

cable, additional cable clamp may be required to give

additional support. Line up the cable on one side of

the pump and maintain as much clearance as possible

on that side when lowering the pump in the well. BE

EXTREMELY CAREFUL NOT TO SCRAPE OR

DAMAGE THE POWER CABLE, CABLE SPLICE

OR GROUNDING SYSTEM WHEN LOWERING

THE PUMP. Hold the power cable up away from the

well casing as lowering the pump into the casing.

6. If the pump does not have a built-in check valve, a line

check valve should be installed within 25 feet above

the pump bowl assembly. For a deep setting pump, a

line check valve is recommended for every 200 feet

of column pipe, However, no check valve should be

installed above the pumping level.

7. As soon as the splice joint is submerged in the water,

take a resistance reading between the power cable

conductors and ground to assure that the insulation

and the cable or the splice was not damaged during

installation.

8. After the last piece of column pipe has been installed,

install the well head. Install a cable clamp between the

last column pipe coupling and the well head base. See

Figure 1. Route the power cable and grounding system

through the large threaded hole in the head base.

Route the air line (if used) through one of the smaller

threaded holes in the head base. The remaining small

threaded hole is for connection of a well vent or other

accessories. All of these holes are threaded with stan-

dard NPT or BSP pipe threads. If a gasket is required

between the head base and its mounting surface, the

gasket should be placed on the foundation prior to

installing the well head.

CAUTION

CAUTION

WARNING

Advertising