5

Technical Data - Frequency Inverter And General Data

HYDROVAR

Hydrovar output to

the Motor

Supply Voltage (Uin)

Prefuse

min.

Type Rated

output

Voltage Max.

current

Mains frequency

48-62 Hz

HV 1.1

1,1 kW

3x 230 V

4,8 A

1x 220-240 V±15%

10 Ampere

HV 1.15

1,5 kW

3x 230V

7,0 A

1x 220-240 V ±15%

10 Ampere

HV 1.2

2,2 kW

3x 230V

10,0 A

1x 220-240 V ±15%

16 Ampere





Output voltage:

3x 0...Uin VAC / 0-70 Hz

(depends on the input voltage)

Min. frequency:

0 – max. frequency

Electrical efficiency:

> 95%




Protection

against: Short circuit, over- and undervoltage, overheating of the

electronics (overload) and additional external protective functions
via PTC (motor temperature) and low water switch.
A mains filter is fitted to ensure interference immunity.


The HV Series frequency converter complies with the general EMC provisions and has
been tested according to the following standards:

• Disturbance voltage:

EN 55011

• EMC – Immunity:

EN 61000-4-3 and ENV 50204

• Electrostatic discharge:

EN 61000-4-2

Ambient temperature:

5° C ... + 40°C

Storage temperature:

-25° C ... + 55° C
(+70°C during max. 24 hours.)

Humidity:

rH max. 50% at 40°C, unlimited

rH max. 90% at 20°C, max. 30 days per year

Condensation not permitted !

Air pollution:

The air may contain dry dust as found in workshops where
there is no excessive quantity of dust due to machines.
Excessive amounts of dust, acids, corrosive gases, salts etc.
are not permitted

Altitude::

max. 1000m above sea level
At higher altitudes the max. available power has to be
reduced. Please ask the manufacturer for further details.

Class of protection :

IP55