15.6 Overheating of the heat sink

XXX

Error KK-Temp

The thermal sensor, mounted on the cooling

body of the HYDROVAR indicates over

temperature. Possible causes: insufficient cooling, ambient temperature is too high or
motor overloaded. After the cause has been remedied, the malfunction has to be
reset by cutting off the power supply for >30 seconds.

15.7 Sensor fault

XXX

Sensor Fault

The voltage level of the incoming analogue
input signal is supervised.

If the signal falls below the 0,5VDC-level, an Error will be displayed.
Possible causes: break of the sensor cable or the sensor itself, bad connection of the
plug of the sensor. After the cause has been remedied, the malfunction has to be reset
by cutting off the power supply for >30 seconds.

15.8 Conveyor limit fault

XXX

Error Water

The value of the programmed Conveyor limit
is not reached within the programmed delay

time Error Delay( see chapter 13.11.1 and 13.11.2).

Possible causes can be: break of the pipe before or after the pump, closed valve before
the pump, air in the pump. After the cause has been remedied, the malfunction has to
be reset by cutting off the power supply for >30 seconds.

15.9 Additional internal processor Error messages:

ERROR 1

:

EEPROM-ERROR
(corresponding data block malfunction)

ERROR 2

:

Not used

ERROR 3

:

Processor RAM error

ERROR 4

:

Not used

ERROR 5

:

Processor ROM error

ERROR 6

:

Watchdog error

ERROR 7

:

Clock error (quarz)

ERROR 8

:

Programme error


These ERROR signals are acknowledged by disconnecting the power supply for

> 30 seconds.
If the error signal should appear again, contact customer service and provide a
detailed description of the error.