13 Settings at the Submenu-Parameter
Important: Before entering the secondary menu these instructions
must be read carefully to prevent incorrect settings which will
cause malfunction.
After entering the SUBMENU PARAMETER, the display
... will change to
PASSWORD
0000
Set Password 0066 by pressing Ï and Ð
PASSWORD
0066
Confirm by pressing Î and the first
parameter of the sub menu is shown
Change Pressure
Enabled
13.1 Pressure change
Change Pressure
Enabled
You can decide between Ï (Enabled) or Ð
(
Disabled)
If the pressure setting is enabled, you can change the required pressure on the
Hydrovarhead with decrease and increase (see chapter 7) without an external
programming device.
Press
Î
on the controller to change to
13.2 Auto start
Auto Start
Enabled
You can select between Ð Disabled and Ï Enabled
Autostart Enabled means, that the pump starts again automatically after an
interruption of the power supply (power failure).
If Autostart Disabled is set, the pump has to be restarted manually after a power
failure, by pressing
and
.
Press
Î
on the controller to change to
Note: The password must be entered at each entry