Instructions:

From the 1

st

display, press the Î button twice, until you

reach

SUBMENU

PARAMETER

Then press the Ð button and the display will change to

PASSWORD

0000

Password:
The Password protection prevents untrained personal from accidentally changing the
base setting

Press the Ï button until you reach the number 0066

PASSWORD

0066

Press the Î button repeatedly until you reach

SUBMENU

CONTROLLER

Press the Ð button to enter the submenu and change to

WINDOW

5,0 %

Now press the Î button until you reach the parameter “LIFT
FREQUENCY”

LIFT FREQUENCY

30 Hz

LIFT FREQUENCY:

This indicates the frequency at which the increase of the set pressure should begin.
It should be the speed at which the pump works at the set pressure and at delivery rate of
0 m³/h. On a 50 Hz system, there is virtually no flow below about 30 Hz, on a 60 Hz
system about 40Hz.

Press the Ï and Ð button until you reach desired frequency.

LIFT FREQUENCY

30 Hz

After changing of the value, you have to confirm with the Î button.
Then you will get the message “SAVE PARAMETER” for a short time, when the new setting
is saved!

Now press the Î button to change to

LIFT INTENSITY

0,0 bar

LIFT INTENSITY:

This value states, how much the required value should be continually increased, till the
maximum speed (maximum volume) is reached. Further description, see chapter 13.6.8.

Press the Ï and Ð button until you reach desired value

LIFT INTENSITY

0,0 bar

After changing of the value, you have to confirm with the Î button.
Then you will get the message “SAVE PARAMETER” for a short time, when the new setting
is saved!

Hold the Î button down for 3 seconds to return to:

SUBMENU

CONTROLLER