Xylem HV 1.1 - 1.2 User Manual

Page 49

Advertising
background image

49

pump has reached the programmed release-frequency. (Adjustable from 0.0 Hz to

70 Hz). If you don’t want to start a following pump this value has to be set higher
than the MAX. FREQUENCY (see chapter 13.5.1)

Press

Î

on the controller to change to

13.7.4 Switch Interval

Switch Interval

24 hours

For changing the master pump and follow-up
pump in order to achieve even operating hours of
the pumps. Adjustable between 0 and 250 hours

To leave the submenu press the Î key longer than 3 sec.!

13.8 Submenu Relay

Submenu

Relay

To enter this menu you have to press the Ð

key, to

leave the menu, press the Î key longer than 3 sec.

13.8.1 Relay Configuration

Relay Configu.

Simple Multicnt.

Possible selections with buttons Ð and Ï:
Simple Multicnt. ⇒ allows to start a following
(simple multi-

constant speed pump.

controller)

(see chapter 13.8.2 / 13.8.3.)

Run Signalling

⇒ Run indication over the relay

Error Signalling ⇒ fault indication over the relay

Attn: Max. contact load 500mA / 125V

Press

Î

on the controller to change to

13.8.2 Start frequency of the slave pump

Slave-On Limit

50,0 Hz

Here you can set the frequency of the speed
controlled HYDROVAR-pump, when the full speed

slave pump should start, if “simple multicontroller” is set in the parameter Relay
configuration (see capter 13.8.1). In this case, the slave pump runs with full speed and
the HYDROVAR-pump controls the additional demand.

Press

Î

on the controller to change to

13.8.3 Stop frequency of the slave pump

Slave-Off Limit

Here you can set the frequency of the speed