When two, three or four Hydrovar speed controlled pumps are connected together in a

system via the RS485-interface, they can be programmed to work together to maintain
system pressure up to the maximum flow rate of all the pumps combined.

As the first pump reaches its maximum speed and flow, the second pump will

automatically turn on (and so on). In addition, the sequence of the pump that will run first

(lead pump) can be automatically varied to reduce premature wear on any one pump in the
system.

Instructions:

!! Refer to chapter 11.1 (setting single pump constant pressure).
Follow these instructions for setting the required pressure and then continue with the
following steps.

From the 1

st

display, press the Î button twice, until you

reach

SUBMENU

PARAMETER

Then press the Ð button and the display will change to

PASSWORD

0000

Password:
The Password protection prevents untrained personal from accidentally changing the
base setting

Press the Ï button until you reach the number 0066

PASSWORD

0066

Press the Î button repeatedly until you reach

SUBMENU

MULTICONTROLLER

Press the Ð button to enter the submenu and change to

ACTUAL VALUE INCREASE

0.15 bar


ACTUAL PRESSURE INCREASE (= Lift value):
This value, together with the fall value (ACTUAL VALUE DECREASE) determines the increase

of the required value after starting of the following pumps (see attached application
example on next page)