12 settings at the invertermenu – Xylem HV 1.1 - 1.2 User Manual

Page 40

Advertising
background image

40

Example:
To change the Hydrovar with address 01 to address 04:

press the Í button to change the * to the left side

Address Change

00* --> 00

Select the address of the Hydrovar, you want to change the
address with the Ï and Ð button

Address Change

01* --> 00

press the Î button to change the * to the right side

Address Change

01 --> 00*

Select the address you want to give this Hydrovar with the
Ï

and Ð button

Address Change

01 --> 04*

To confirm and save the new selected address press both buttons (Íand Î) together
for 2 sec. If it was successfully you will see the same address on both sides.

Address Change

04 --> 04*


The definition of the address you have to do for each pump in the system.

Hold the Î button down for 3 seconds to return to:

SUBMENU

Address

Hold the Î button down again for 3 seconds to return to
the 1

st

display

PRESSURE x.x bar

SPEED xx Hz

12 Settings at the Invertermenu

1

st

display

PRESS X.X bar

SPEED X.X Hz

The actual input value [bar] and the actual
output frequency [Hz] are displayed.

Press

Î

on the controller to change to

PRESSURE

XX.X bar

There you can set required pressure
with the buttons Ï

and Ð

Press

Î

on the controller to change to

SUBMENU

PARAMETER

To enter the submenu “Parameter”,
press Ð

button

Press

Î

on the controller to change to 1

st

display