Xylem HV 1.1 - 1.2 User Manual

Page 51

Advertising
background image

51

Press

Î

on the controller to change to

13.10.2 Sequence for automatic test run

Time Test Run

100 h

Adjustable between 1...100 hours.
The test run starts the pump at the set time after

the last stop for 20 seconds with the in parameter 13.10.3 set speed.
Deactivating test run: Set 0 hours, by using Ï

and Ð.

Repeating the test run: Select test run and set the desired hours using the key

Ï

.

Press

Î

on the controller to change to

13.10.3 Test Run: Frequency

Test Frequency

30.0 Hz

Frequency for manual and automatic test run.
Can be set from 0 Hz up to 70 Hz.

Press

Î

on the controller to change to

13.10.4 Test Run: Boost

BOOST Test Run

10.0 %.

Start voltage in % of rated voltage in order to ensure
that the motor starts safely. Adjustable between 0%
and 25%

To leave the submenu press the Î key longer than 3 sec.!

13.11 Submenu Error

Submenu

Error

To enter this menu you have to press the Ð

key, to

leave the menu, press the Î key longer than 3 sec.

13.11.1 Conveyor Limit

Conveyor Limit

0.0 bar

Disabled or adjustable between 0 and 10 bar of the
analogue input signal range.

0.0 bar” means disabled conveyor limit.
An adjusted value >0 has to be reached till the programmed “ERROR DELAY”-time.
Doesn’t this value be reached the failure “ERROR WATER” will be indicated and the
pump stops.

Press

Î

on the controller to change to

13.11.2 Error Delay