13.3 Mode

Mode

Controller

Select with buttons Ð and Ï between:
Multicontroller ⇒ sequence control for max. 4 pumps

Controller ⇒ pressure control for a single pump If only one HYDROVAR-pump is in
operation, set Controller.

If more than one HYDROVAR-pumps are working together via the RS485-interface, the
Multicontroller must be selected.
Actuator ⇒ external frequency setting. The application Actuator is only used, if you

have an external controller and the HYDROVAR works like a standard frequency
converter (external frequency signal 0,5-4,5VDC to the terminals X2/1 and X2/2).

Press

Î

on the controller to change to

13.4 Control Response

Regulation Mode

Normal

Normal: Speed is increased with falling actual value
Signals. (e.g.: Control at constant output pressure).
Inverse: Speed is reduced with falling actual value
signal, (e.g.: Control of constant suction pressure or at
constant level before the pump).

Press

Î

on the controller to change to

13.4.1 Dimension unit

Dimension unit

Bar

Here you could choose your favourite unit (with
buttons Ð and Ï) Bar, psi or % for the 1

st

display.

Press

Î

on the controller to change to

13.5 Submenu Inverter

Submenu

Inverter

To enter this menu you have to press the Ð

key, to

leave the menu, press the Î key longer than 3 sec.

Press

Î

on the controller to change to

13.5.1 Maximum Frequency

Max. Frequency

50.0 Hz

Possible setting between min. 40 and max. 70 Hz.

Attention: Settings higher than 50 Hz may overload the

motor!

Settings of 10% above nominal frequency cause 33%
more power consumption!