increase of the required value after starting of the following pumps (see attached

application example in chapter 13.7.2)

Press

Î

on the controller to change to

13.7.2 Fall Value
For scaling the required value for 1 to 4 pumps

Actu. Value Dec.

0.15 bar

Adjustable between 0 and 2,5 bar.
This value determines the start value of the 2

nd

and the

other following pumps. (Start-Value = REQUIRED VALUE – ACT. VALUE DEC.)

Application example:
1) Pump 1 reaches f

max

(maximum speed )

2) Pressure falls and reaches the start-value of the 2

nd

pump

(= REQUIRED VALUE – ACTU. VALUE DEC.)

3) Pump 2 is switched on automatically
4) The required value is calculated new, after the start of the 2

nd

pump in the

following way!


New required value
= REQUIRED VALUE – ACTU. VALUE DEC. + ACU. VALUE INC.



Generally:

k ... Number of active pumps (k >1)

P = P

set

+ (k-1)*[lift value – fall value]

• Lift value = Fall value ⇒ Pressure constant when pumps switch on
• Lift value > Fall value ⇒ Pressure rises when lag-pump switches on
• Lift value < Fall value ⇒ Pressure falls when lag-pump switches on

Press

Î

on the controller to change to

13.7.3 Release – Follow up pump

Enable Seq. Ctl.

48.0 Hz

The follow-up pump only starts, when the start-
value is reached (see chapter 13.7.2) and the lead