Enter the required value by pressing the Ï and Ð button

ACTUAL VALUE INCREASE

0,15 bar

After changing of the value, you have to confirm with the Î button.
Then you will get the message “SAVE PARAMETER” for a short time, when the new setting
is saved!

Press the Î button to change to

ACTUAL VALUE DECREASE

0,15 bar

ACTUAL PRESSURE DECREASE (= Fall value):

This value determines amount of pressure drop you will allow before the next pump starts.

(see application example on previous page)

Enter the required value by pressing the Ï and Ð button

ACTUAL VALUE DECREASE

0,15 bar

After changing of the value, you have to confirm with the Î button.
Then you will get the message “SAVE PARAMETER” for a short time, when the new setting
is saved!

Press the Î button to change to

ENABLE SEQ. CONTROL

48 Hz

ENABLE SEQUENCE CONTROL:

The follow-up pump only starts, when the start-value is reached (see chapter 13.7.2) and
the lead pump has reached the programmed release-frequency. (Adjustable from 0.0 Hz to
70 Hz). Normally this start frequency is set 1 to 2Hz lower than the MAX. FREQUENCY (see

chapter 13.5.1)
If you don’t want to start a following pump this value has to be set higher than the MAX.
FREQUENCY. (see application example on previous page)

Enter the required value by pressing the Ï and Ð button

ENABLE SEQ. CONTROL

49 Hz

After changing of the value, you have to confirm with the Î button.
Then you will get the message “SAVE PARAMETER” for a short time, when the new setting
is saved!

Press the Î button to change to

SWITCH INTERVAL

24 HOURS

SWITCH INTERVAL

This time determines the interval of the changeover of the master pump in order to
achieve even operating hours of all pumps in the system. Adjustable between 0 and 250
hours

Enter the required value by pressing the Ï and Ð button

SWITCH INTERVAL

24 HOURS