a) motor cable:

Locate the motor connections, labeled U, V, W inside the Hydrovar. Connect wires to the

terminals and rout the cable through the cable gland.

You must take a motor cable at least Ø 11.5mm if you want protection IP55. (only HV1.1)


The earth-wire of the cable has to be fixed with the screws with the earth-symbol to the
cooling body of the Hydrovar.

Connections in the conduit box

The connection of the motor cable depends on the type of the motor and can be done in
star or delta connection:
(you have to use the connection for a motor voltage of 3x230V shown on the motor label)


Star-connection Delta-connection



b) supply cable

The main power cable is connected to the terminals labelled L1, N for the 230 VAC, single
phase input (shown in the diagram 6.2.2.1).