Xylem HV 1.1 - 1.2 User Manual

Page 28

Advertising
background image

28

General for working with the external programming device:


With Í and Î you can select the different parameters in the menu.

To enter a submenu, press the Ð button. To leave the submenu, you have to press
the buttons Í or Î for longer than 3 sec.
With Ï or Ð you can change the parameters.
Each change in the settings is saved after leaving this parameter with the buttons
Í

or Î.

When you have changed a parameter and you leave it, the LCD shows you the
following message

SAVE

PARAMETER

for about 2 sec.

10

Connecting the external programming device to the HYDROVAR

After connection of the HYDROVAR – head to the power supply and plug in of the
external programming device, there can be shown two different messages:

1. If the AUTOCONNECTION (14.1.1) is disabled (standard) you reach:

Address 01

Lost

This message is shown, when the Remote Control is
new connected

At this time the Hydrovar searches for an available address

If address 01 is available, the display changes to

Address 01

Detected

The actual pump-address is shown

Statusinformations by systems with activated Multicontroller:

P1: Masterpump

P2: Slavepump
P3: Slavepump
P4: Slavepump
P.: Follownumber is not useful

Hold: pump stops through the pressure transmitter
Run: pump runs
Stop: pump stops through the leadpump
Disabled: pump stops through the stopbutton or the terminal block
Error: pump stops through an error

Ð

Follow pump stopped

Ï

Regulator from the follow pump is release

Pump don’t work at the follow pump

Advertising