2 usage of the auxiliary voltage, Usage of the auxiliary voltage -40, Warning – YSI DIQ/S 182-PR System 182 User Manual

Page 54: Caution, Terminal strip diq/s 182-pr terminal strip diq/chv, Valve control line

Advertising
background image

Installation

System 182

3 - 40

ba76024e01

02/2012

Warning

No free wires must be allowed to project into the enclosure.
Otherwise, there is a danger that areas safe to contact could come
into contact with dangerous voltages. This could result in life
threatening electric shock when working with the Universal
Transmitter. Always cut off any wires that are not in use as closely
as possible to the cable gland.

3.9.2

Usage of the auxiliary voltage

The Universal Transmitter has a 24 V output (designation,
HILFSSPANNUNG or AUXILIARY VOLTAGE on the terminal strip).
You can use this auxiliary voltage for the relay-controlled opening of the
valve in a DIQ/CHV valve module for the compressed air-driven sensor
cleaning function. To do so, you have to connect the auxiliary voltage
output, a free relay contact and the valve connection in the DIQ/CHV in
series. Bridge a terminal of the auxiliary voltage output with a terminal
of a relay output and run a control line from the remaining terminals to
the valve module.

Caution

The auxiliary voltage must not be used for other purposes.

Connection scheme for one sensor with compressed air cleaning

17

Close the enclosure of the Universal Transmitter.

X13

X15

X6

X12

X14

X5

X11

X4

X10

X3

X9

X2

X8

X1

Terminal strip
DIQ/S 182-PR

Terminal strip
DIQ/CHV

R1

AUXILIARY

VOLTAGE

VALVE

DISTRUBUTION

R2

R3

Valve
control line