2.6 Grounding Requirements, CE-3x2 5K-T

The ground rod system is typically used in remote applications where the generator is located

away from the power supply enclosure and exposed to lightning strikes, or coincidental

surges. The wiring interface between the DC Genset and system carries a system ground to

ensure common ground between both cabinets and communication devices. The remote APU

cabinet ground rod serves only as an alternate discharge path.

Alpha Technologies recommends using the grounding method illustrated below. The grounding method for a particular site will be

dependant upon soil type, available space, local codes, NEC (National Electric Code), and other site- specific characteristics.

Alpha Technologies recommends 5 ohms minimum ground resistance between enclosure and ground rods, in accordance with IEEE

1100-1999 Powering and Grounding Electronic Equipment. NEC minimum grounding standard is 25 ohms.

Alpha Technologies assumes no responsibility or liability for failure of the installer to comply with the requirements of all applicable local

and national codes. Where allowed, exothermic welding may be used as an alternative to Burndy clamps and connectors.

Fig. 2-11, Enclosure Grounding, CE-3x2 5K-T

(for reference only)

5

7

8

9

4

3

10

1

2

6

NOTE:

Service grounding (required). #6AWG Copper wire from

service entrance ground bar.

Two ground rods, 6' apart

Lightning protection (optional). 1/2" x 8' Copper ground

rods, 4 places.

Burndy YGHP58C2W-3 or equivalent compression ground

tap connector

#6 bare copper wire from loop to enclosure ground bar

1

2

3

4

5

Burndy YGHP58C2W-3 or equivalent compression ground

tap connector

Terminate at ground bar

Terminate at ground bar

#6 bare copper loop terminated at each ground rod, 30” below

grade (min). Corrosion-proof (25 yr. life-span) connections

suitable for direct burial MUST be used

#2 AWG wire

6

7

8

9

10