2 enclosure installation procedure, pn-6x-t 7.5kw, Warning – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48Vdc User Manual

Page 40

Advertising
background image

40

042-288-B0-001, Rev. A2

Fig. 3-11, Installation Location of Pad Shear/

Magnet Assembly

(Dimensions in inches)

3.0

Installation, continued
3.3

PN-6x-T 7.5kW Installation, continued

3.3.2 Enclosure Installation Procedure, PN-6x-T 7.5kW

1. Position the enclosure above the concrete pad and slowly lower it into position

over the pad’s 3/8" (or 1/2") anchor or J-bolts. A 25+ year vapor barrier MUST be

used between the concrete and enclosure base to inhibit moisture ingress, and

to prevent possible corrosion caused by metal to concrete contact. The vapor

barrier material (such as Alpha P/N 564-721-10) should initially extend at least

1/2" in all directions around the perimeter of the enclosure. After the enclosure is

in place, the material should be cut closer to the enclosure, using the appropriate

knife or cutting tool.

2. Secure the enclosure using customer-supplied stainless, galvanized (or better),

flat washers, lock washers and 3/8" (or 1/2") nuts at each mounting bolt. Torque

mounting hardware in accordance with manufacturers’ ratings.

3. The pad shear sensor is located in the left hand corner of the enclosure from the

rear door. To install, locate the loose magnet (located in a plastic bag included

with the enclosure). Remove the two screws holding the sensor in place, and lift

out. Using a silicone based glue, glue the loose magnet to the pad in the center

of the hole. After the glue has set, install the sensor with the two Phillips screws

so it faces the glued down magnet.

If a pedestal is used, relocate the pad shear sensor to the L-bracket located near

the bottom of the pedestal. Glue the pad shear magnet directly below the sensor.

Use the extender cable to connect the pad shear sensor wires to the wires

located in the generator enclosure (route wires through pad shear sensor hole in

the floor of the generator enclosure).

The pad shear sensor is a safety feature that

must be correctly installed before connecting

the gas utility. This is a CRITICAL safety feature required to disable the generator in the

event of automobile impact, seismic, or other unforeseen catastrophic event.

To prevent damage to the enclosure, it must be mounted flush to a completely flat surface. If the

concrete pad is uneven or has bumps, cracks or other imperfections, the installer is responsible for

correcting these defects prior to installing the enclosure.

CAUTION!

WARNING!

ENCLOSURE

FRONT

0.25

3.00

5.35

5.60

0.581

3.40