0 maintenance, Table 7-1, scheduled maintenance, Maintenance procedures – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48Vdc User Manual

Page 75

Advertising
background image

042-288-B0-001, Rev. A2

75

7.0 Maintenance

The engine/alternator requires maintenance at regular intervals to remain reliable and ready to

provide backup power when needed. Please refer to the following table for general maintenance

guidelines. For specific recommendations regarding maintenance intervals, please refer to the

supplied engine manufacturer’s operator’s manual.

Maintenance Procedures: X = Action, R = Replace as necessary

Frequency: D = Daily, W = Weekly, M = Monthly, Q = Quarterly, AS = Attended Startup, S = Six Months

Y = Yearly (all numbers in hours)

Table 7-1, Scheduled Maintenance

System Component or

Procedure

Visual Inspection

Verify

Change

Clean

Test

Frequency

FUEL

Inspect flexible lines and

connections

X

R

Q

Check fuel supply

X

W or AS

Inspect fuel piping

X

Y

LUBRICATION

Check oil level

X

X

D, AS

Change oil

R

Y or 100

Replace oil filter

R

Y or 100

COOLING

Verify air ducts, filters, and

free from debris

X

X

Y or AS

EXHAUST SYSTEM

Check for leakage. carbon or

soot residue indicates leaks.

Repair immediately.

X

X

X

Y

Check for fire hazards

X

Y

Check for loose or broken

hangers and supports.

Clean exhaust outlet

X

R

Y or AS

BATTERY CONNECTIONS

Check battery charger

operation, charge rate

X

M

Clean, re-torque battery

terminals

X

X

X

Y or 100

ELECTRICAL SYSTEM

General inspection

X

Q

Inspect cables for abrasion

(Generator compartment)

X

X

S

Reapply corrosion-inhibiting

coating on all exposed

connector assemblies

X

Y

ENGINE & MOUNTING

General insp ection

X

W

Inspect air cleaner element

R

Y or 100

Inspect spark plugs

R

Y or 500

CONTROL SYSTEM

Verify remote control operation

X

M

Run generator set

X

W

GENERATOR SET

Inspect generator set

X

Prestart

Exercise generator set

X

M

GENERAL CONDITION OF

EQUIPMENT

Check for signs of damage due

to vibration, leakage,

excessive noise, extreme

temperature, or deterioration.

X

X

X

W

Inspect and clean cabinet

interior

X

X

Q or AS

Maintenance Procedures

louvers are

Advertising
This manual is related to the following products: