042-288-B0-001, Rev. A2

73

6.0 Operation

6.1 Normal Operating Condition

Under normal operating conditions (no alarms) the ECM’s RAS switch is in the AUTO

position. The ECM has control over the APU while in Auto mode. Each time the RAS switch

is moved from the STOP position to the AUTO position, the ECM, after a short delay, runs

the APU for one minute. This indicates that the ECM is in the Auto mode, and is capable of

starting and stopping the APU automatically. The APU can be controlled manually by placing

the RAS switch in the RUN or STOP positions. In Auto mode, the ECM continuously monitors

the AC line voltage, DC bus voltage, enclosure sensors, and APU status. If a fault occurs, the

ECM determines whether to start or inhibit the APU based on the type of fault.

6.1.1 AC Line Fail

Standby Operating Condition Less Than Three Minutes

If an AC line disturbance or outage is less than three minutes, the ECM will not start

the APU unless the battery bus voltage drops below a programmable threshold (Low

DC Bus Level). The default is 49V. The ECM will notify the system operator of a line

failure via the front panel LEDs, and through the AC Fail Relay located on Terminal

Block 2 (see Table 3-1).

Standby Operating Condition More Than Three Minutes

If an AC line disturbance or outage is longer than three minutes, the ECM start delay

timer expires and the ECM starts the APU. The ECM starts and runs the APU until

either a normal shutdown or major alarm occurs. If the APU fails to start, the ECM

attempts to start the engine up to nine times, with either 30 or 60 second intervals

between attempts. If the engine will not start, the ECM reports an Engine Over-crank

alarm.

6.1.2 Low DC Bus Level

If the DC bus voltage level drops to 49Vdc, or below, the APU will start. The APU

continues to run until the ECM DC Sense Voltage increases to 53.5Vdc or higher.

Once the ECM DC Sense Voltage level is reached, and the 12-minute cool-down

period expires, the APU will stop.

The 53.5Vdc threshold is set to assure rectifiers are supporting the DC bus before

the generator goes into cool down and shuts off. The level assumes a rectifier set

point of 54.5Vdc at 25°C and a battery temperature compensation of -70mV/c.

** Note: Under very hot battery temperature conditions the voltage threshold may not

be eclipsed by rectifier output until temperatures cool.