4 charger module control interface connector, 3 gas solenoid interface connector – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48Vdc User Manual

Page 90

Advertising
background image

90

042-288-B0-001, Rev. A2

Fig. 8-3, Gas Solenoid Interface Connector

Fig. 8-4, Charger Control Interface Connector

8.4 Charger Module Control Interface Connector

The Charger Module – Control Interface Connector is connected between the

charger module and ECM with Sense/Power leads connected to the APU output DC bus. The

interface control is a 4-pin (2x2 row) Universal Mini Mate-’N’-Lok style male connector.

8.0

Interconnection, continued

8.3 Gas Solenoid Interface Connector

Pin Description

Function

1

ECM Charger Control

(+) Yellow Wire

Connects pins 1 and 2 together, turning the charger

ON, i.e. Closed (LOW signal).

2

Inverter Battery

(+) Red Wire

Input power to charger module, operates on 48Vdc

battery pack to charge ignition battery.

3

ECM Charger Control

Orange Wire

ECM turns charger ON by applying a LOW signal to

this pin (referenced to ignition battery negative).

4

Inverter Battery (-)

Black Wire

NEGATIVE input power to charger module, operates

on 48Vdc battery pack to charge ignition battery.

Pin Description

Function

1

Gas Solenoid +12V

+12Vdc supplied to gas solenoid only when APU is ON

(running). APU Shuts OFF gas supply to cabinet during

any fail safe or fault condition.

2

Gas Solenoid Common

Return path for gas solenoid.

Advertising
This manual is related to the following products: